Abstract
This paper presents a preliminary study of torsional interaction between turbine-generator system and inverter based distributed generation. Small-signal stability based on eigenvalue analysis is used to observe this condition. The multimass turbine model is included in the overall distributed generation system model. Two case studies are demonstrated to observe the torsional interaction in the distributed generation system. It can be shown that under stand-alone operation, unstable oscillatory modes may occur and highly influenced by the operating points of the system.
Original language | English |
---|---|
Title of host publication | Proceedings of the Universities Power Engineering Conference |
Publisher | IEEE Computer Society |
Volume | 2011-January |
Edition | January |
Publication status | Published - 2011 |
Event | 2011 46th International Universities' Power Engineering Conference, UPEC 2011 - Soest, Germany Duration: 2011 Sept 5 → 2011 Sept 8 |
Other
Other | 2011 46th International Universities' Power Engineering Conference, UPEC 2011 |
---|---|
Country/Territory | Germany |
City | Soest |
Period | 11/9/5 → 11/9/8 |
ASJC Scopus subject areas
- Energy Engineering and Power Technology