抄録
An influence of the voltage sag magnitude and duration on nonutility generator's mechanical shaft torque is investigated by simulations using the Electromagnetic Transients Program (ATP-EMTP). Various types of fault are simulated, changing the fault point, the number of faulted phases and the voltage phase angle at the moment of fault occurring. From the simulation results, it becomes clear that the high-speed static switchgear is effective for the stable operation of the in-house generation systems and the critical loads, which are subjected to the voltage sag.
本文言語 | English |
---|---|
ホスト出版物のタイトル | 2000 IEEE Power Engineering Society, Conference Proceedings |
出版社 | Institute of Electrical and Electronics Engineers Inc. |
ページ | 153-158 |
ページ数 | 6 |
巻 | 1 |
ISBN(印刷版) | 0780359356, 9780780359352 |
DOI | |
出版ステータス | Published - 2000 |
イベント | IEEE Power Engineering Society Winter Meeting, 2000 - Singapore, Singapore 継続期間: 2000 1月 23 → 2000 1月 27 |
Other
Other | IEEE Power Engineering Society Winter Meeting, 2000 |
---|---|
国/地域 | Singapore |
City | Singapore |
Period | 00/1/23 → 00/1/27 |
ASJC Scopus subject areas
- エネルギー工学および電力技術
- 電子工学および電気工学