抄録
The results of laboratory measurements on the performance of a floor-supply displacement air-conditioning system in comparison to a displacement ventilation system with a side-wall-mounted diffuser and a ceiling-based distribution system are described. Thermal stratification was observed, as there were greater vertical air temperature differences in both of the displacement systems than in the ceiling-based system. The floor-supply displacement air-conditioning system produced a uniformly low air velocity at each measurement height, while a rather high air velocity near the floor was observed for the displacement ventilation system with a sidewall-mounted diffuser. Local mean age of air of the floor-supply displacement air-conditioning system was lower than that of the other systems, especially in the lower part of the room. According to the simulation results, the floor-supply displacement air-conditioning system with outdoor air cooling requires 34% less energy than the conventional air-conditioning system with outdoor air cooling.
本文言語 | English |
---|---|
ページ(範囲) | PART 2/- |
ジャーナル | ASHRAE Transactions |
巻 | 105 |
出版ステータス | Published - 1999 12月 1 |
外部発表 | はい |
イベント | ASHRAE Annual Meeting - Seattle, WA, USA 継続期間: 1999 6月 18 → 1999 6月 23 |